Ground Wire Size Calculator (NEC 250.122 Standard)

[Area Iklan Google AdSense - Top Post]

Ground wire size calculator based on NEC 250.122 Standard

Does this calculator work for service entrance? Of course not. This is for equipment grounding (EGC) based on breaker size (Table NEC 250.122), not for service grounding (Table 250.66).

⏚ Grounding Size Calculator

Based on NEC Table 250.122 (Safety Standards)

*Enter the Ampere rating of the Circuit Breaker protecting the equipment.
Minimum Grounding Wire Size:
Compliance Note:
Based on NEC 250.122 for Copper.
*Metric (mm²) values are approximate conversions for reference.
[Iklan Tengah Artikel - Disisipkan Otomatis]

What is grounding in electrical?

Grounding or earthing in the engineering is the connection of an electrical system to the soil (earth).

It creates a direct and low resistance path for excess electricity to dissipate safely into the ground, rather than passing through a person or sensitive equipment. This can prevent the electric shock to harm people and damaging equipment.

What is ground wire size chart?

Ground wire size refers to the physical thickness of the minimum cable size for safety that connect electrical equipment to the earth (ground). This ground wire usually have the color yellow & green.

Ground wire size table base on NEC

There is no formula in determining the ground wire size. We should look at the NEC table and NEC chart as the base on determining the ground wire size.

Table: NEC 250.122 - Minimum Ground Wire Size

Use this table to quickly find the Equipment Grounding Conductor (EGC) size based on your circuit breaker rating.

Breaker / Fuse Rating (Amps) Copper Wire Size (Cu) Aluminum Wire Size (Al)
15 Amps 14 AWG 12 AWG
20 Amps 12 AWG 10 AWG
60 Amps 10 AWG 8 AWG
100 Amps 8 AWG 6 AWG
200 Amps 6 AWG 4 AWG
300 Amps 4 AWG 2 AWG
400 Amps 3 AWG 1 AWG
500 Amps 2 AWG 1/0 AWG
600 Amps 1 AWG 2/0 AWG
800 Amps 1/0 AWG 3/0 AWG
1000 Amps 2/0 AWG 4/0 AWG
Source: NFPA 70 (National Electrical Code), Table 250.122
[Iklan Tengah Artikel - Disisipkan Otomatis]

Nec based ground wire size chart

NEC Table 250.122 Cheat Sheet

Minimum Size of Equipment Grounding Conductors
Breaker Rating
(Overcurrent Device)
Copper Wire
(Most Common)
Aluminum Wire
(Aluminum/CCA)
15 Amps 14 AWG 12 AWG
20 Amps 12 AWG 10 AWG
30 - 60 Amps 10 AWG 8 AWG
100 Amps 8 AWG 6 AWG
200 Amps 6 AWG 4 AWG
300 Amps 4 AWG 2 AWG
400 Amps 3 AWG 1 AWG
500 Amps 2 AWG 1/0 AWG
600 Amps 1 AWG 2/0 AWG
800 Amps 1/0 AWG 3/0 AWG
1000 Amps 2/0 AWG 4/0 AWG
1200 Amps 3/0 AWG 250 kcmil
1600 Amps 4/0 AWG 350 kcmil
2000 Amps 250 kcmil 400 kcmil
Note: Data is based on NFPA 70 National Electrical Code (NEC). If the breaker size falls between standard ratings (e.g., 70A), use the wire size for the next higher rating (e.g., use the 100A row).

Understanding NEC 250.122

We talked much about NEC. What is it? In the world of electrical engineering, determining the size of the equipment grounding conductor (EGC) correctly is a MUST. It is very critical for safety. The contractors / installers / applicators must ensure that if a fault occurs, the breaker must immediately trip, otherwise it will be very dangerous and causes electric shock.

ground wire size

Now, engpocket friends already know how to determine the ground wire size, we are wonder, do you eager to use our watts to amps calculator and converting 3 phase and single phase on this link? Check it out