Breaker size calculator
⚡ Engineering Breaker Calculator
Recommended Breaker Size:
…
…
This calculator is the hybrid version of 3 phase breaker size calculator & single phase breaker calculator. later in this post, we will give you the breaker size chart too. Stay tuned.
Electricity is one of the most important things in our daily lives. One of the vital components in electricity is the MCB (Miniature Circuit Breaker).
Get to know the MCB
MCB stands for Miniature Circuit Breaker. It is an automatic electrical switch designed to protect an electrical circuit from damage caused by overload or short circuit. MCB 1 phase has 1 toggle switch, MCB 3 phase have 3 toggle switches. These toggle switch only have 2 positions, on and off.
Some of engpocket friends must be asking yourself, “why don’t we use fuse?”. MCB is different with fuse, which operates once and must be replaced, MCB can be reset. We just have to flip the toggle switch from the OFF position back to ON position after the MCB trips.

MCB single phase vs MCB 3 phase. Spot the difference
| Feature | Single Phase MCB (1P) | Three Phase MCB (3P) |
|---|---|---|
| Number of Poles | Has 1 Pole (input and output for Phase line only). | Has 3 Poles (input and output for R, S, T / L1, L2, L3 lines). |
| Physical Size | Slim and narrow (usually 1 module width). | Wide and bulky (usually 3x the width of a 1-Phase MCB). |
| Voltage Rating | Designed for 220V – 240V (Standard Household). | Designed for 380V – 415V (Industrial/Commercial). |
| Application | Used for lights, outlets, and small appliances (TV, Fridge, AC < 2 PK). | Used for large motors, elevators, big chillers, and factory machines. |
| Trip Mechanism | Protects a single line. If it trips, only that specific line goes off. | Common Trip: If one phase has a fault, the lever pulls ALL three phases down simultaneously. |
Breaker size formula
Do you want to know how the breaker size formula worked?
Pay attention to below formula, based on the breaker size calculator:
Case 1: Input is in Volt-Amperes (VA)
This is apparent power, so we don’t use the Cos φ.
- Single-phase (220V):
I=220PVA
- Three-phase (380V line-to-line):
I=3×380PVA≈658PVA
Case 2: Input is in Watts (W)
This requires power factor (Cos φ) to convert to apparent power first:
- Single-phase:
I=220×PFPW
- Three-phase:
I=3×380×PFPW≈658×PFPW
Case examples
1 phase case
An engpocket electrician is upgrading a kitchen. A new induction cooker hood (3.5 kW) and oven (2.5 kW) are being installed on the same circuit.
- Total load = 3500 W + 2500 W = 6000 W
- 1-phase, 220V in standard residential
- Estimated power factor ≈ 0.95 (modern appliances)
Standard breakers come in steps (25A, 32A…), so he can’t use a 25A, it would trip. So, he should install a 32A MCB 1 Phase
3 phase case
Rocky manages a small auto repair shop. A new 3 phase air compressor (7.5 kW motor) is delivered into his place. The nameplate says: 380V, 3 phase, 15 A full-load current.
Even though the motor says it is 15 A, he could not install a 16A breaker. Why?
- Motors have inrush current (5–7× running current at startup).
- Standards (like IEC 60947) require MCB with higher tolerance (often Type C or D magnetic trip).
So, he must select:
A 25A 3-pole MCB (Type C)
Breaker size chart
As a compliment of the breaker size calculator, here we provide you the breaker size chart too
📋 Reference Chart: Single Phase (220V)
| MCB Size | Max Load (Amps) | Max Capacity (VA) | Max Power (Watt)* |
|---|---|---|---|
| 2 Amp | 2 A | 440 VA | 352 W |
| 4 Amp | 4 A | 880 VA | 704 W |
| 6 Amp | 6 A | 1,320 VA | 1,056 W |
| 10 Amp | 10 A | 2,200 VA | 1,760 W |
| 16 Amp | 16 A | 3,520 VA | 2,816 W |
| 20 Amp | 20 A | 4,400 VA | 3,520 W |
| 25 Amp | 25 A | 5,500 VA | 4,400 W |
| 32 Amp | 32 A | 7,040 VA | 5,632 W |
| 40 Amp | 40 A | 8,800 VA | 7,040 W |
| 50 Amp | 50 A | 11,000 VA | 8,800 W |
| 63 Amp | 63 A | 13,860 VA | 11,088 W |
🏭 Reference Chart: 3 Phase (380V)
| MCB Size (3-Pole) | Max Load (Amps) | Max Capacity (kVA)** | Max Power (kW)* |
|---|---|---|---|
| 6 Amp | 6 A | 3.9 kVA | 3.1 kW |
| 10 Amp | 10 A | 6.5 kVA | 5.2 kW |
| 16 Amp | 16 A | 10.5 kVA | 8.4 kW |
| 20 Amp | 20 A | 13.1 kVA | 10.5 kW |
| 25 Amp | 25 A | 16.4 kVA | 13.1 kW |
| 32 Amp | 32 A | 21.0 kVA | 16.8 kW |
| 40 Amp | 40 A | 26.3 kVA | 21.0 kW |
| 50 Amp | 50 A | 32.9 kVA | 26.3 kW |
| 63 Amp | 63 A | 41.4 kVA | 33.1 kW |
| 80 Amp | 80 A | 52.6 kVA | 42.1 kW |
| 100 Amp | 100 A | 65.8 kVA | 52.6 kW |
| 125 Amp | 125 A | 82.2 kVA | 65.8 kW |
| 160 Amp | 160 A | 105.2 kVA | 84.2 kW |
| 200 Amp | 200 A | 131.6 kVA | 105.2 kW |
| 250 Amp | 250 A | 164.5 kVA | 131.6 kW |
Note: For continuous loads, it is recommended to use only 80% of the breaker capacity (Safety Factor).
If engpocket friends wanted to use BTU to PK calculator to calculate the and decided air conditioner capacity, you can visit this post link.